5.7 H: Terminal Functions
H parameters are used to assign functions to the external terminals.
◆
H1: Multi-Function Digital Inputs
■
H1-01 to H1-06: Functions for Terminals S1 to S6
These parameters assign functions to the multi-function digital inputs. The settings 0 to 7E determine function for each
terminal and are explained below.
Note:
If not using an input terminal or if using the through-mode, set that terminal to “F”.
Table 5.16 Digital Multi-Function Input Settings
No.
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.
Parameter Name
Setting
Range
Default
H1-01
Multi-Function Digital Input S1 Terminal Function Selection 1 to 7E
40 (F): Forward Run Command (2-wire sequence)
H1-02
Multi-Function Digital Input S2 Terminal Function Selection 1 to 7E
41 (F): Reverse Run Command (2-wire sequence)
H1-03
Multi-Function Digital Input S3 Terminal Function Selection 0 to 7E
24: External Fault
H1-04
Multi-Function Digital Input S4 Terminal Function Selection 0 to 7E
14: Fault Reset
H1-05
Multi-Function Digital Input S5 Terminal Function Selection 0 to 7E
: Multi-Step Speed Reference 1
H1-06
Multi-Function Digital Input S6 Terminal Function Selection 0 to 7E
: Multi-Step Speed Reference 2
Setting
<1> This setting is valid from software versions 6000 or later.
Function
Page
Setting
Function
Page
0
3-Wire Sequence
20 to 2F
External Fault
1
LOCAL/REMOTE Selection
30
PID Integral Reset
2
External Reference 1/2
31
PID Integral Hold
3
Multi-Step Speed Reference 1
34
PID Soft Starter Cancel
4
Multi-Step Speed Reference 2
35
PID Input Level Selection
5
Multi-Step Speed Reference 3
40
Forward Run/Stop (2-wire sequence)
6
Jog Reference Selection
41
Reverse Run/Stop (2-wire sequence)
7
Accel/Decel Time 1
42
Run/Stop (2-Wire sequence 2)
8
Baseblock Command (N.O.)
43
FWD/REV (2-Wire sequence 2)
9
Baseblock Command (N.C.)
44
Offset Frequency 1 Addition
A
Accel/Decel Ramp Hold
45
Offset Frequency 2 Addition
B
Drive Overheat Alarm (oH2)
46
Offset Frequency 3 Addition
C
Terminal A1/A2 Enable/Disable
Node Setup
F
Not used/Through Mode
50
Disturb Function Cancel
10
Up Command
51
Synchronous Accel/Decel
11
Down Command
53
Energy Saving On/Off
12
Forward Jog
59
DC Injection Braking 1
13
Reverse Jog
60
DC Injection Braking 2
14
Fault Reset
61
External Speed Search Command 1
15
Fast-Stop (N.O.)
62
External Speed Search command 2
16
Motor 2 Selection
65
KEB 1 (N.C.)
17
Fast-stop (N.C.)
66
KEB 1 (N.O.)
18
Timer Function Input
67
Communications Test Mode
19
PID Disable
7C
Short-Circuit Braking (N.O.)
1A
Accel/Decel Time Selection 2
7D
Short-Circuit Braking (N.C.)
1B
Program Lockout
7E
Forward/Reverse Detection (V/f Control with
Simple PG Feedback)