B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
337
Pa
ra
met
er
Li
st
B
14
Fault Reset
Closed: Resets faults if the cause is cleared and the Run command is
removed.
O
O
O
15
Fast-Stop (N.O.)
Closed: Decelerates at the Fast-Stop time C1-09.
To restart the Fast-Stop input must be released and Run must be cycled.
O
O
O
16
Motor 2 Selection
Open: Motor 1 (E1-
, E2-
)
Closed: Motor 2 (E3-
, E4-
)
O
O
–
17
Fast-stop (N.C.)
Open: Decelerates according to C1-09 (Fast-stop Time)
O
O
O
18
Timer Function Input
Set the timer delay using parameters b4-01 and b4-02.
Ensure this function is set in conjunction with the multi-function output
timer (H2-
= 12).
O
O
O
19
PID Disable
Closed: PID control disabled
O
O
O
1A
Accel/Decel Time Selection 2
Switches Accel/Decel times.
O
O
O
1B
Program Lockout
Open: Parameters can not be edited. (except U1-01 if reference source is
set for operator)
Closed: Parameters may be edited and saved.
O
O
O
20 to 2F
External Fault
20: N.O., Always Detected, Ramp To Stop
21: N.C., Always Detected, Ramp To Stop
22: N.O., During Run, Ramp To Stop
23: N.C., During Run, Ramp To Stop
24: N.O., Always Detected, Coast To Stop
25: N.C., Always Detected, Coast To Stop
26: N.O., During Run, Coast To Stop
27: N.C., During Run, Coast To Stop
28: N.O., Always Detected, Fast-stop
29: N.C., Always Detected, Fast-stop
2A: N.O., During Run, Fast-stop
2B: N.C., During Run, Fast-stop
2C: N.O., Always Detected, Alarm Only (continue running)
2D: N.C., Always Detected, Alarm Only (continue running)
2E: N.O., During Run, Alarm Only (continue running)
2F: N.C., During Run, Alarm Only (continue running)
O
O
O
30
PID Integral Reset
Closed: Resets the PID control integral value.
O
O
O
31
PID Integral Hold
Closed: Maintains the current PID control integral value.
O
O
O
34
PID Soft Starter
Closed: Disables the PID soft starter b5-17.
O
O
O
35
PID Input Switch
Closed: Inverses the PID input signal
O
O
O
40
Forward Run Command (2-Wire
sequence)
Open: Stop
Closed: Forward run
Note:
Can not be set together with Settings 42 or 43.
O
O
O
41
Reverse Run Command (2-Wire
sequence)
Open: Stop
Closed: Reverse run
Note:
Can not be set together with Settings 42 or 43.
O
O
O
42
Run Command (2-Wire sequence 2)
Open: Stop
Closed: Run
Note:
Can not be set together with Settings 40 or 41.
O
O
O
43
FWD/REV Command (2-Wire
sequence 2)
Open: Forward
Closed: Reverse
Note:
Can not be set together with Settings 40 or 41.
O
O
O
44
Offset Frequency 1 Addition
Closed: Adds d7-01 to the frequency reference.
O
O
O
45
Offset Frequency 2 Addition
Closed: Adds d7-02 to the frequency reference.
O
O
O
46
Offset Frequency 3 Addition
Closed: Adds d7-03 to the frequency reference.
O
O
O
Node Setup
Closed: Set up the node address.
O
O
O
50
Disturb Function Cancel
Open: Disturb function output is active.
Closed: Cancels the Disturb function.
O
O
O
51
Synchronous Accel/Decel
Closed: Assigns the same accel/decel times to all motors in the line so
that they reach the desired frequency at the same time.
O
O
O
53
Energy Saving On/Off
Closed: Enables the Energy Saving function.
O
O
×
59
DC Injection Braking 1 Command
Closed: Triggers DC Injection Braking 1 (b2-02)
O
O
×
H1 Multi-Function Digital Inputs Settings
H1-
Setting
Function
Description
Control
Mode
Pg.
V/f OL
V PM