B.6 Defaults by Drive Model Selection (o2-04)
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
369
Pa
ra
met
er
Li
st
B
No.
Description
Unit
Default Settings
−
Model CIMR-TC
−
2V0010
2V0012
2V0020
C6-01
Duty Mode Selection
−
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
o2-04
Drive Model Selection
Hex.
65
66
68
E2-11
(E4-11,
T1-02)
Motor rated power
kW
1.5
2.2
2.2
3.0
3.7
5.5
b3-06
Output Current 1 during Speed Search
−
0.5
0.5
0.5
0.5
0.5
0.5
b8-04
Energy Saving Coefficient Value
−
169.4
156.8
156.8
136.4
122.9
94.75
C6-02
Carrier Frequency Selection
−
3
1
3
1
3
1
E2-01
(E4-01,
T1-04)
Motor Rated Current
A
6.2
8.5
8.5
11.4
14
19.6
E2-02
(E4-02)
Motor Rated Slip
Hz
2.6
2.9
2.9
2.7
2.73
1.5
E2-03
(E4-03)
Motor No-Load Current
A
2.8
3.0
3.0
3.7
4.5
5.1
E2-05
(E4-05)
Motor Line-to-Line Resistance
Ω
1.997
1.601
1.601
1.034
0.771
0.399
E2-06
(E4-06)
Motor Leakage Inductance
%
18.5
18.4
18.4
19
19.6
18.2
E2-10
(E4-10)
Motor Iron Loss for Torque
Compensation
W
53
77
77
91
112
172
E5-01
PM Motor Code Selection
hex
0005
0005
0006
0006
0008
0008
L2-02
Momentary Power Loss Ride-Thru Time
s
0.3
0.3
0.5
0.5
1
1
L2-03
Momentary Power Loss Minimum
Baseblock Time
s
0.4
0.5
0.5
0.5
0.6
0.7
L2-04
Momentary Power Loss Voltage
Recovery Ramp Time
s
0.3
0.3
0.3
0.3
0.3
0.3
L2-05
Undervoltage Detection Level (Uv1)
V dc
190
190
190
190
190
190
L8-02
Overheat Alarm Level
°C
100
100
100
100
110
110
L8-09
Output Ground Fault Detection Selection
−
0
0
0
0
0
0
L8-35
Installation Method Selection
−
0
0
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
−
1
1
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
10
n9-12
On-Delay Compensation Time
ms
1.80
1.80
1.80
1.80
1.60
1.60
S6-01
DC Bus Capacity
μ
F
800
800
1100
1100
2100
2100
S6-02
Motor Acceleration Time
s
1.66
1.45
1.45
1.45
1.54
1.68