5.7 H: Terminal Functions
180
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Setting 1: 0 to 10 Vdc without Lower Limit
The input level is 0 to 10 Vdc. Negative input values will be accepted. Refer to the explanation of H3-01, Setting 1.
to Setting 1: 0 to 10 Vdc without Limit on page 178
Setting 2: 4 to 20 mA Current Input
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0 (like setting 0).
Setting 3: 0 to 20 mA Current Input
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0 (like setting 0).
■
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2.
Refer to Multi-Function Analog Input Terminal Settings
for a list of functions and descriptions.
■
H3-11, H3-12: Terminal A2 Gain and Bias Setting
Parameter H3-11 sets the level of the selected input value that is equal to 10 Vdc/20 mA input at terminal A2 (Gain).
Parameter H3-12 sets the level of the selected input value that is equal to 0 Vdc/4 mA/0 mA input at terminal A2.
Both can be used to adjust the analog input A2 characteristics. The setting works in the same way as parameters H3-03
and H3-04 for analog input A1.
■
H3-13: Analog Input Filter Time Constant
Parameter H3-13 sets the time constant for a first order filter that will be applied to both analog inputs A1 and A2.
An analog input filter can be used to prevent erratic drive control when a “noisy” analog reference is used. The drive
operation becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing
analog signals.
■
Multi-Function Analog Input Terminal Settings
This section describes the various functions that can be assigned to terminal A1 and A2 by setting H3-02 and H3-10.
Note:
The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values
when selecting and adjusting analog input functions.
No.
Name
Setting Range
Default
H3-10
Terminal A2 Function Selection
0 to 1F
0
No.
Name
Setting Range
Default
H3-11
Terminal A2 Gain Setting
-999.9 to 999.9%
100.0%
H3-12
Terminal A2 Bias Setting
-999.9 to 999.9%
0.0%
No.
Name
Setting Range
Default
H3-13
Analog Input Filter Time Constant
0.00 to 2.00 s
0.03 s
Setting
Function
Page
Setting
Function
Page
0
Frequency Bias
F
Not used/Through Mode
1
Frequency Gain
10
Forward Torque Limit
2
Auxiliary Frequency Reference
11
Reverse Torque Limit
4
Output Voltage Bias
12
Regenerative Torque Limit
7
Overtorque/Undertorque Detection Level
15
General Torque Limit
B
PID Feedback
16
Differential PID Feedback
C
PID Set Point
1F
Not used/Through Mode
E
Motor Temperature (PTC input)