5.4 d: Reference Settings
146
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
■
d2-05: Frequency Reference 2 Lower Limit
Sets the lower limit for the frequency reference value that is input from frequency reference source 2 (b1-15). The limit
applies to any source selected in parameter b1-15. The value is set as a percentage of the maximum output frequency.
If a lower reference than this value is input, the drive will run at the d2-05 level. If the drive is started with a lower
reference than d2-05, it will accelerate up to d2-05.
◆
d7: Offset Frequency
■
d7-01 to d7-03: Offset Frequency 1 to 3
Three different offset values can be added to the frequency reference. They can be selected using digital inputs
programmed for Offset frequency 1, 2 and 3 (H1-
= 44, 45, 46). The selected offset values are added if two or all
three inputs are closed at the same time.
Note:
This function can be used to replace the “Trim Control” function (H1-
= 1C/1D) of earlier Yaskawa drives.
illustrates the Offset Frequency Function.
Figure 5.32
Figure 5.32 Offset Frequency Operation
No.
Parameter Name
Setting Range
Default
d2-05
Frequency Reference 2 Lower Limit
0.0 to 110.0%
0.0%
No.
Parameter Name
Setting Range
Default
d7-01
Offset Frequency 1
-100.0 to 100.0%
0%
d7-02
Offset Frequency 2
-100.0 to 100.0%
0%
d7-03
Offset Frequency 3
-100.0 to 100.0%
0%
Frequency
reference
Offset Frequency 1 [d7-01]
(Signed)
Offset Frequency 2 [d7-02]
(Signed)
Offset Frequency 3 [d7-03]
(Signed)
Multi-function
input (44) = on
Multi-function
input (45) = on
Multi-function
input (46) = on
SFS
Frequency
reference after
soft starter