5.2 b: Application
112
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Setting 0: Run Command Must Be Cycled
If the Run command is issued differently in the old and new control source (e.g. old - terminals, new - serial
communications) and it is active at the new source when switching takes place, the drive will either not start or it will
stop if it was running before. The Run command has to be cycled to start from the new control source.
Setting 1: Continue Running
If the Run command is active at the new control source, the drive starts or continues running. There is no need to cycle
the Run command.
WARNING!
The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel away from rotating
machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.
■
b1-08: Run Command Selection while in Programming Mode
As a safety precaution, the drive will not normally respond to a Run input when the digital operator is being used to
adjust parameters in the Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-Tuning). If
required by the application b1-08 can be used to changed this functionality.
Setting 0: Disabled
A Run command is not accepted while the digital operator is in Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit Programming During Run
It is not possible to enter the Programming Mode as long as the drive output is active.
■
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Setting 0: Standard Phase Order
Setting 1: Switched Phase Order
■
b1-15: Frequency Reference Source 2
This frequency reference is enabled when one of the multi-function inputs set for External Reference 1/2 (H1-
= 2)
closes.
Refer to Setting 1: LOCAL/REMOTE Selection on page 160
for instructions on using an external frequency
Refer to b1-01: Frequency Reference Source 1 on page 106
for details on the frequency reference selection
as governed by parameter b1-01..
No.
Parameter Name
Setting Range
Default
b1-07
LOCAL/REMOTE Run Selection
0 or 1
0
No.
Parameter Name
Setting Range
Default
b1-08
Run Command Selection while in Programming Mode
0 to 2
0
No.
Parameter Name
Setting Range
Default
b1-14
Phase Order Selection
0 or 1
0
No.
Parameter Name
Setting Range
Default
b1-15
Frequency Reference Source 2
0 to 4
0