A Specifications
YASKAWA ELECTRIC
TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
165
S
p
ec
ifi
c
at
ions
A
■
Altitude Derating
The drive standard ratings are valid for an installation altitude up to 3000 m (9842 ft.). If the altitude exceeds 1000 m
(3280 ft.). both the drive rated voltage and the rated output current must be derated for 1% per 100 m (328 ft.). The
maximum altitude is 3000 m (9842 ft.).
Environmen
t
Area of Use
Indoors
Ambient Temperature
IP00 enclosure with top protective cover: [-10 to 40°C (14 to 104°F)]
IP00 enclosure: [-10 to 50°C (14 to 122
°
F)]
Humidity
95 RH% or less (no condensation)
Storage Temperature
[-20 to 60°C (-4 to 140
°
F)] (short-term temperature during transportation)
Altitude
Up to 1000 meters (3280 ft.) without derating, up to 3000 meters (9842 ft.) with output current and
voltage derating
Vibration/Shock
10 to 20 Hz: 9.8 m/s
2
20 to 55 Hz: 5.9 m/s
2
(CIMR-LU2
0008 to 2
0180, 4
0005 to 4
0150, and 5
0003 to
5
0077) or 2.0 m/s
2
(CIMR-LU2
0215 to 2
0415, 4
0180 to 4
0260, and 5
0099 to
5
0200)
Standards
• UL Underwriters Laboratories Inc:
UL508C Power Conversion Equipment
• IEC/EN 61800-3, IEC/EN 61800-5-1
• ISO International Organization for Standardization:
ISO/EN 13849-1 Cat. 3 PLd Safety of machinery - Safety-related parts of control systems (models
CIMR-L
A
)
ISO/EN 13849-1 Cat. 3 PLe Safety of machinery - Safety-related parts of control systems (models
CIMR-L
F
)
• IEC International Electrotechnical Commission:
IEC/EN 61508 SIL2 Functional safety of electrical/electronic/programmable electronic
safety-related systems safety integrity level 2 (models CIMR-L
A
)
IEC/EN 61508 SIL3 Functional safety of electrical/electronic/programmable electronic
safety-related systems safety integrity level 3 (models CIMR-L
F
)
• CSA Canadian Standards Association International
:
2411-02 Elevator Equipment - Enclosed Elevator-and Escalator Electrical Equipment
3211-06 Industrial Control Equipment - Motor Controllers - Miscellaneous
C22.2 No.04-04 Bonding and Grounding of Electrical Equipment
C22.2 No.14-05 Industrial Control Equipment
B44.1/ASME-A17.5-2004 Safety Code for Elevators and Escalator Electrical Equipment used by
CSA to evaluate the L1000 to Class 2411 (Elevator Equipment)
• ANSI/ASME American Society of Mechanical Engineers/American National Standards Institute:
ANSI/ASME A17.1-2007/B44-04 Safety Code for Elevators and Escalators, Dumbwaiters,
Moving Walks, Material Lifts, and Dumbwaiters with Automatic Transfer Devices using IEC/EN
12016:2004 immunity requirements.
ANSI/ASME-A17.5-2004/CSA B44.1 - Elevator and Escalator Electrical Equipment, used by
CSA to evaluate the L1000 to Class 2411 (Elevator Equipment)
Protection Design
IP00 enclosure with top protective cover, IP00
<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different
motors and with changing motor temperature. Contact Yaskawa for consultation.
<2> For drives with B or earlier as the design revision order, 50 Hz is required. The design revision order and software version are printed on the
nameplate affixed to the side of the drive.
Refer to Model Number on page 16
for details.
<3> Overload protection may be triggered when operating with 150% of the rated output current if the output speed is less than 6 Hz.
<4> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground
fault is present at the output.
<5> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-2, ISO/EN
13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
Item
Specification
TOEP_C710616_38H_7_0.book 165 ページ 2015年11月11日 水曜日 午後7時40分