3 Electrical Installation
YASKAWA ELECTRIC
TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
55
El
ec
tr
ical
I
n
st
al
lat
io
n
3
■
Sinking/Sourcing Mode Selection for Safe Disable Inputs
Use jumper S3 on the terminal board to select between Sink mode, Source mode or external power supply for the Safe
Disable inputs H1 and H2 as shown in
(Default: Sink mode, internal power supply).
Table 20 Safe Disable Input Sink / Source / External Power Supply Selection
◆
Connect to a PC
This drive is equipped with a USB port (type-B).
The drive can connect to a USB port on a PC using a USB 2.0, AB-type cable (sold separately). After connecting the
drive to a PC, Yaskawa DriveWizard Plus software can be used to monitor drive performance and manage parameter
settings. Contact Yaskawa for more information on DriveWizard Plus.
Download and install the USB driver before connecting L1000A to a PC with the USB cable.
To obtain the driver and software of USB Copy Unit, CopyUnitManager and DriveWizardPlus, access these sites:
U.S.A: http://www.yaskawa.com
Other areas: contact a Yaskawa representative.
Figure 29
Figure 29 Connecting to a PC (USB)
Drive Internal Power Supply
External 24 Vdc Power Supply
Sinking Mode
Sourcing Mode
24 Vdc
H1
H2
HC
Jumper S3
24 Vdc
H1
H2
HC
External
24 Vdc
Jumper S3
24 Vdc
H1
H2
HC
Jumper S3
24 Vdc
H1
H2
HC
External
24 Vdc
Jumper S3
PC
(Type-B)
(Type-A)
USB Cable
(Type-AB)
Y E A
TOEP_C710616_38H_7_0.book 55 ページ 2015年11月11日 水曜日 午後7時40分