3 Electrical Installation
50
YASKAWA ELECTRIC
TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Wire Size and Torque Specifications
WARNING!
Fire hazard. Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in
death or serious injury by fire due to overheating of electrical connections. Improperly tightened terminal screws can also cause
erroneous equipment operation.
Select appropriate wire type and gauges from
. For simpler and more reliable wiring, use crimp ferrules on the
wire ends. Refer to
for ferrule terminal types and sizes.
Table 17 Wire Gauges and Torque Specifications
Ferrule-Type Wire Terminals
Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire
ends with insulated sleeves before connecting to the drive. Refer to
for dimensions.
Figure 25
Figure 25 Ferrule Dimensions
Table 18 Ferrule Terminal Types and Sizes
Terminal
Block
Terminal
Screw
Size
Tightening
Torque
N
m
(lb.in.)
Bare Wire Terminal
Ferrule-Type Terminal
Wire Type
Applicable
Wire
Size
mm
2
(AWG)
Recomm.
mm
2
(AWG)
Applicable
Wire
Size
mm
2
(AWG)
Recomm.
mm
2
(AWG)
TB1, TB2
TB3, TB4
FM, AC, AM, P1,
P2, PC, SC, A1,
A2, A3, +V, -V, S1
to S8, MA, MB,
MC, M1, M2, HC,
H1, H2, DM+,
DM-, IG,
R+, R-, S+, S-,
RP, MP
M3
0.5 to 0.6
(4.4 to 5.3)
Stranded wire:
0.2 to 1.0
(24 to 17)
Solid wire:
0.2 to 1.5
(24 to 16)
0.75
(18)
0.25 to 0.5
(24 to 20)
0.5
(20)
Shielded wire,
etc.
E (G)
1.0 (16)
TB5
E (G)
M3.5
0.5 to 1.0
(4.4 to 8.9)
0.5 to 2
(20 to 14)
1.25
(12)
–
–
Size mm
2
(AWG)
Type
L mm (in)
d1 mm (in)
d2 mm (in)
Manufacturer
0.25 (24)
AI 0.25-8YE
12.5 (0.49)
0.8 (0.03)
2 (0.08)
PHOENIX CONTACT
0.34 (22)
AI 0.34-8TQ
12.5 (0.49)
0.8 (0.03)
2 (0.08)
0.5 (20)
AI 0.5-8WH
AI 0.5-8OG
14 (0.55)
1.1 (0.04)
2.5 (0.10)
d1
d2
8 mm
(0.31 in.)
L
YEA_common
TOEP_C710616_38H_7_0.book 50 ページ 2015年11月11日 水曜日 午後7時40分