C Standards Compliance
YASKAWA ELECTRIC
TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
229
St
an
dar
d
s
Co
mplia
nce
C
Note:
Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum
allowable temperature of 7
5°
C (167
°
F) 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed
40
°
C (104
°
F).
Table 64 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
4
0370
R/L1, S/L2, T/L3
300
×
2P
4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
300
×
2P
4/0 to 300
–, +1
–
3/0 to 300
+3
–
3/0 to 300
1
1 to 3/0
4
0450
R/L1, S/L2, T/L3
3/0
×
4P
3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
4/0
×
4P
3/0 to 300
–, +1
–
1/0 to 300
+3
–
1/0 to 300
1/0
1/0 to 300
4
0605
R/L1, S/L2, T/L3
300
×
4P
4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
300
×
4P
4/0 to 300
–, +1
–
1/0 to 300
+3
–
1/0 to 300
2/0
2/0 to 300
<1> Drive models CIMR-LU4
0045 to 4
0260 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
<2> When an EMC filter is installed, take additional measures to comply with IEC/EN 61800-5-1. Refer to
EMC Filter Installation on page 220
for details.
Model
CIMR-LU
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N
m (lb.in.)
5
0003
5
0004
R/L1, S/L2, T/L3
14
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
–, +1, +2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
5
0006
R/L1, S/L2, T/L3
14
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
–, +1, +2
–
14 to 10
B1, B2
–
14 to 10
10
12 to 10
5
00010
R/L1, S/L2, T/L3
10
14 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
14
14 to 6
–, +1, +2
–
14 to 6
B1, B2
–
14 to 10
8
12 to 8
M5
2.0 to 2.5
(17.7 to 22.1)
5
0013
R/L1, S/L2, T/L3
10
10 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
10
10 to 6
–, +1, +2
–
10 to 6
B1, B2
–
10 to 8
2.7 to 3.0
(23.9 to 26.6)
8
12 to 8
M6
5.4 to 6.0
(47.8 to 53.1)
Model
CIMR-LU
Terminal
Recommended
Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
Screw
Size
Tightening Torque
N
m (lb.in.)
TOEP_C710616_38H_7_0.book 229 ページ 2015年11月11日 水曜日 午後7時40分