7 Option Card Installation
YASKAWA ELECTRIC
TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
159
Op
tion
Ca
rd
In
st
al
lat
io
n
7
Crimp Terminals
Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent crimp terminals with the specifications
listed in
for wiring to ensure proper connections.
Note:
Properly trim wire ends so loose wire ends do not extend from the crimp terminals.
Table 54 Crimp Terminal Sizes
6.
Route the option wiring.
Depending on the drive model, some drives may require routing the wiring through the side of the front cover to
the outside. For drive models CIMR-LU2
0008 through 2
0033, 4
0005 through 4
0018, and 5
0003
through 5
0010, cut out the perforated openings on the left side of the drive front cover as shown in
and leave no sharp edges to damage wiring.
Route the wiring inside the enclosure as shown in
-B for drive models CIMR-LU2
0047 through
2
0415, 4
0024 through 4
0605, and 5
0013 through 5
0200 that do not require routing through the front
cover.
Figure 86
Figure 95 Wire Routing Examples
Wire Gauge
mm
2
Phoenix Contact Model
L
mm (in)
d1
mm (in)
d2
mm (in)
0.25 (24 AWG)
AI 0.25 - 6YE
AI 0.25 - 6BU
10.5 (13/32)
0.8 (1/32)
2 (5/64)
0.34 (22 AWG)
AI 0.34 - 6TQ
10.5 (13/32)
0.8 (1/32)
2 (5/64)
0.5 (20 AWG)
AI 0.5 - 6WH
12 (15/32)
1.1 (3/64)
2.5 (3/32)
A – Route wires through the openings
provided on the left side of the
front cover.
(CIMR-LU2
0008 through 2
0033,
4
0005 through 4
0018, and
5
0003 through 5
0010)
<1> The drive will not meet IP20/NEMA 1, UL Type 1 requirements if wiring is exposed outside the
enclosure.
B – Use the open space provided
inside the drive to route option
wiring.
(CIMR-LU2
0047 through 2
0415,
4
0024 through 4
0605, and
5
0013 through 5
0200)
d1
d2
6 mm
(0.24 in.)
L
B
A