SIEPC71061737B GA800 Drive Technical Reference
107
3.8
External Interlock
For applications that will have unwanted effects on the system if the drive stops, make an interlock between fault
relay output (MA, MB, MC) and the MFDO
DriveReady
signal.
◆
Drive Ready
When the drive is operating or is prepared to accept a Run command, the MFDO terminal to which
Drive Ready [H2-
xx = 6]
is set will enter the ON status.
In these conditions, Drive Ready is OFF and the drive ignores Run commands:
•
The drive is de-energized
•
During a fault
•
There is problem with the control power supply
•
There is a parameter setting error that will not let the drive run, although a Run command is entered
•
An overvoltage or undervoltage fault occurs when the Run command is entered
•
The drive is in Programming Mode.
◆
Interlock Circuit Example
Refer to
for an example of how two drives that run one application use the Drive Ready and Fault output
signals to interlock with the controller.
Terminal
Output Signal
Parameter Settings for Output Signal
MA, MB, MC
Fault
-
M1-M2
Drive Ready
H2-01 = 6
Figure 3.55 Interlock Circuit Example
Summary of Contents for GA80U4720ABM
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...