YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
349
Code
Name
Causes
Possible Solutions
The following parameters are set at the same time:
•
b1-01 = 4 [Pulse Train Input]
•
H6-01 ≠ 0 [Terminal RP Pulse Train Function ≠
Frequency Reference]
Set
H6-01 = 0
.
The following parameters are set at the same time:
•
F3-01 = 6 [Digital Input Function Selection =
BCD (5-digit), 0.01 Hz]
•
F3-03 = 0, 1 [Digital Input Data Length Select =
8-bit, 12-bit]
Set
F3-03 = 2 [16-bit]
.
These parameters are set and there is an AI-A3 option
card connected to the drive:
•
H1-xx = 2 [External Reference 1/2 Selection]
•
b1-15 = 3 [Frequency Reference Selection 2 =
Option PCB]
•
F2-01 = 0 [Analog Input Function Selection = 3
Independent Channels]
Correct the parameter settings.
Code
Name
Causes
Possible Solutions
oPE06
Control Method Selection Error
A1-02 = 1, 3, or 7 [Control Method Selection = CL-
V/f, CLV, CLV/PM]
is set, but there is no encoder
option card connected to the drive.
•
Connect an encoder option card to the drive.
•
Set
A1-02
correctly.
Code
Name
Causes
Possible Solutions
oPE07
Analog Input Selection Error
The settings for
H3-02, H3-06, and H3-10 [MFAI
Function Select]
and
H7-30 [Virtual Analog Input
Selection]
overlap.
Set
H3-02, H3-06, H3-10, and H7-30
correctly to prevent overlap.
Note:
It is possible to set these functions to multiple analog input
terminals at the same time:
•
Setting value
0 [Frequency Reference]
•
Setting values
F and 1F [Not Used]
The following parameters are set at the same time:
•
H3-02, H3-06, H3-10, H7-30 = B [PID Feedback]
•
H6-01 = 1 [Terminal RP Pulse Train Function =
PID Feedback Value]
The following parameters are set at the same time:
•
H3-02, H3-06, H3-10, H7-30 = C [PID Setpoint]
•
H6-01 = 2 [PID Setpoint Value]
The following parameters are set at the same time:
•
H3-02, H3-06, H3-10, H7-30 = C
•
b5-18 = 1 [b5-19 PID Setpoint Selection =
Enabled]
The following parameters are set at the same time:
•
H6-01 = 2
•
b5-18 = 1
Remove the function settings that are not in use.
Code
Name
Causes
Possible Solutions
oPE08
Parameter Selection Error
You set a function that is not compatible with the
control method set in
A1-02 [Control Method
Selection]
.
1.
Push
to show
U1-18 [oPE Fault Parameter]
, and find
parameters that are not in the applicable setting range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other
oPExx
errors have priority over
oPE02
.
When
A1-02 = 2 [Control Method Selection = OLV]
,
you used these parameter settings:
•
n2-02 > n2-03 [Automatic Freq Regulator Time 1
> Automatic Freq Regulator Time 2]
•
C4-02 > C4-06 [Torque Compensation Delay
Time > Motor 2 Torque Comp Delay Time]
•
Set
n2-02 < n2-03
.
•
Set
C4-02 < C4-06
.
When
A1-02 = 0 [Control Method Selection = V/f]
,
you used these parameter settings:
•
H6-01 = 3 [Terminal RP Pulse Train Function =
Speed Feedback (V/F Control)]
•
H1-xx = 16 [MFDI Function Select = Motor 2
Selection]
Correct the parameter settings.
Note:
You cannot use Speed Feedback (V/F Control) with the Motor
Switch function.
When
A1-02 = 5 [PM Open Loop Vector]
, you set
E5-02 to E5-07 [PM Motor Parameters] = 0
.
•
Set
E5-01 [PM Motor Code Selection]
correctly as specified by
the motor.
•
For specialized motors, refer to the motor test report and set
E5-
xx
correctly.
Summary of Contents for GA80U4720ABM
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...