6.3 MEMOBUS/Modbus Communications
290
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Register No.
(Hex.)
Description
002A
Minor Fault Description 1
bit 0 - 1
Reserved
bit 2
EF [FWD/REV Run Command Input Error]
bit 3
bb [Baseblock]
bit 4
oL3 [Overtorque 1]
bit 5
oH [Heatsink Overheat]
bit 6
ov [Overvoltage]
bit 7
Uv [Undervoltage]
bit 8
Reserved
bit 9
CE [Modbus Communication Error]
bit A
bUS [Option Communication Error]
bit B
UL3/UL4 [Undertorque Detection 1/2]
bit C
oH3 [Motor Overheat (PTC Input)]
bit D
FbL [PID Feedback Loss], FbH [Excessive PID Feedback]
bit E
Reserved
bit F
CALL [Serial Comm Transmission Error]
002B
U1-10 [Input Terminal Status]
bit 0
1: Control circuit terminal S1 ON
bit 1
1: Control circuit terminal S2 ON
bit 2
1: Control circuit terminal S3 ON
bit 3
1: Control circuit terminal S4 ON
bit 4
1: Control circuit terminal S5 ON
bit 5
1: Control circuit terminal S6 ON
bit 6
1: Control circuit terminal S7 ON
bit 7
1: Control circuit terminal S8 ON
bit 8 - F
Reserved
Summary of Contents for GA80U4720ABM
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...