YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
727
Table 12.32 Example Settings of MFAO Terminals to Monitor Speed Waveforms
No.
Name
Setting Value
Description
H4-01
Terminal FM Analog Output Select
116
Lets you use terminal FM to monitor
U1-16
[SFS Output Frequency]
.
H4-02
Terminal FM Analog Output Gain
100.0%
H4-03
Terminal FM Analog Output Bias
0.0%
H4-04
Terminal AM Analog Output Select
105
Lets you use the terminal AM to monitor
U1-05 [Motor Speed]
.
H4-05
Terminal AM Analog Output Gain
50.0%
H4-06
Terminal AM Analog Output Bias
0.0%
H4-07
Terminal FM Signal Level Select
1
Lets you monitor in a -10 to +10 V range.
H4-08
Terminal AM Signal Level Select
1
These settings cause this MFAO configuration. The MFAO common is terminal AC:
•
Terminal FM: Outputs the output frequency after SFS in a -10 V to +10 V (-100% to +100%) range.
•
Terminal AM: Outputs the motor speed in a -10 V to +10 V (-200% to +200%) range.
Yaskawa recommends that you monitor the output frequency after SFS and the motor speed for delays in response
and differences in reference values.
■
Adjust ASR Parameters
Use
to adjust ASR. The table shows the parameters for motor 1. To operate motor 2, set the motor 2
parameters in the same method.
Note:
When adjusting the proportional gain and integral time, adjust the proportional gain first.
Table 12.33 ASR Response and Possible Solutions
Problem
Possible Solutions
Speed response is slow.
•
Increase
C5-01/C5-03 [ASR Proportional Gain]
.
•
Decrease
C5-02/C5-04 [ASR Integral Time]
.
Overshoot or undershoot occurs at the end of acceleration
or deceleration.
•
Decrease
C5-01/C5-03
.
•
Increase
C5-02/C5-04
.
Vibration and oscillation occur at constant speed.
•
Decrease
C5-01/C5-03
.
•
Increase
C5-02/C5-04
.
•
Increase
C5-06 [ASR Delay Time]
.
Speed accuracy is unsatisfactory when you operate a motor
that has a large quantity of rated slip in Closed Loop V/f
Control.
•
Check the pulse number set to
F1-01 [Encoder 1 Pulse
Count (PPR)]
and the gear ratio set to
F1-12 [Encoder 1
Gear Teeth 1]
and
F1-13 [Encoder 1 Gear Teeth 2]
.
•
Make sure that you correctly set the pulse signal from
the encoder.
•
Check
U6-04 [ASR Output]
to make sure that the ASR
operates at its output limit set to
C5-05 [ASR Limit]
. If
the ASR is at the output limit, increase
C5-05
.
Summary of Contents for GA80U4720ABM
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...