Parameters
Speed Estimation
Current Detection 2
b3-24 = 1
b3-24 = 2
b3-06 [Speed Estimation Current Level 1]
x
-
b3-07 [Speed Estimation Current Level 2]
x
-
b3-08 [Speed Estimation ACR P Gain]
x
-
b3-09 [Speed Estimation ACR I Time]
x
-
b3-10 [Speed Estimation Detection Gain]
x
-
b3-14 [Bi-directional Speed Search]
x
○
b3-17 [Speed Est Retry Current Level]
x
x
b3-18 [Speed Est Retry Detection Time]
x
x
b3-19 [Speed Search Restart Attempts]
x
x
b3-24 [Speed Search Method Selection]
x (1)
x (2)
b3-25 [Speed Search Wait Time]
x
x
b3-26 [Direction Determination Level]
x
-
b3-27 [Speed Search RUN/BB Priority]
x
x
b3-29 [Speed Search Back-EMF Threshold]
-
-
b3-31 [Spd Search Current Reference Lvl]
-
x
b3-32 [Spd Search Current Complete Lvl]
-
x
b3-33 [Speed Search during Uv Selection]
x
x
b3-35 [Low Back EMF Detection Level]
x
x
b3-36 [High Back EMF Detection Level]
x
x
b3-54 [Search Time]
-
-
b3-55 [Current Increment Time]
-
-
b3-56 [InverseRotationSearch WaitTime]
-
x
Note:
•
To use Speed Estimation Speed Search with V/f Control, do Rotational Auto-Tuning before you set the Speed Search function. If the wire
length between the drive and motor changed since the last time you did Auto-Tuning, do Stationary Auto-Tuning for Line-to-Line
Resistance process again.
•
If
A1-02 = 5, 6 [PM Open Loop Vector, PM Advanced Open Loop Vector]
and the wiring distance between the motor and drive is long or if
the motor is coasting at more than or equal to 200 Hz, do not use Speed Search to restart the motor. Use Short Circuit Braking.
■
Current Detection 2
Use this Speed Search function with induction motors. Set
b3-24 = 2 [Speed Search Method Selection = Current
Detection 2]
. Current Detection Speed Search injects current into the motor to detect the speed of an induction motor.
Speed Search increases the output voltage for the time set in
L2-04 [Powerloss V/f Recovery Ramp Time]
, starting
from the maximum output frequency or the frequency reference.
Summary of Contents for GA80U4720ABM
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...