938
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Note:
•
When you use this method to set the torque limit, it enables the lower torque limit:
–
Set
H3-02
,
H3-06
, or
H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit]
.
–
Use a communication option to set the torque limits
•
You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect
oC
[Overcurrent]
.
•
If you set the value too low with large loads, the motor can stall.
■
L7-02: Reverse Torque Limit
No.
(Hex.)
Name
Description
Default
(Range)
L7-02
(04A8)
RUN
Reverse Torque Limit
Sets the torque limit value for reversed motoring as a percentage, where motor rated torque is the
100% value.
200%
(0 - 300%)
Note:
•
When you use this method to set the torque limit, it enables the lower torque limit:
–
Set
H3-02
,
H3-06
, or
H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit]
.
–
Use a communication option to set the torque limits
•
You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect
oC
[Overcurrent]
.
•
If you set the value too low with large loads, the motor can stall.
■
L7-03: Forward Regenerative Trq Limit
No.
(Hex.)
Name
Description
Default
(Range)
L7-03
(04A9)
RUN
Forward Regenerative Trq
Limit
Sets the torque limit value for forward regenerative conditions as a percentage of the motor rated
torque.
200%
(0 - 300%)
Note:
•
When you use this method to set the torque limit, it enables the lower torque limit:
–
Set
H3-02
,
H3-06
, or
H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit]
.
–
Use a communication option to set the torque limits
•
You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect
oC
[Overcurrent]
.
•
If you set the value too low with large loads, the motor can stall.
■
L7-04: Reverse Regenerative Trq Limit
No.
(Hex.)
Name
Description
Default
(Range)
L7-04
(04AA)
RUN
Reverse Regenerative Trq
Limit
Sets the torque limit value for reversed regenerative conditions as a percentage of the motor rated
torque.
200%
(0 - 300%)
Note:
•
When you use this method to set the torque limit, it enables the lower torque limit:
–
Set
H3-02
,
H3-06
, or
H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit]
.
–
Use a communication option to set the torque limits
•
You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect
oC
[Overcurrent]
.
•
If you set the value too low with large loads, the motor can stall.
■
L7-06: Torque Limit Integral Time
No.
(Hex.)
Name
Description
Default
(Range)
L7-06
(04AC)
Torque Limit Integral Time
Sets the integral time constant for the torque limit function.
200 ms
(5 - 10000 ms)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA80U4720ABM
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...