Set
A1-02 = 4 [Control Method Selection = AOLV]
and
n4-72 = 1 [Speed Feedback Mode = With Encoder]
to use
this parameter.
Parameter
F1-02 [Encoder Signal Loss Detect Sel]
sets the drive response when the drive detects a disconnected
encoder. This parameter sets the drive to start up in the Without Encoder Mode or With Encoder Mode if the drive
detects
PGo [Encoder (PG) Feedback Loss]
.
Note:
A PG-B3 encoder option is necessary to use this parameter. When you use a PG-X3 option, it is not necessary to set this parameter.
If the drive detects
PGo
, de-energize the drive and examine the wiring for the encoder.
0 : Without Encoder
1 : With Encoder
■
n4-74: Limit of Flux Loop
No.
(Hex.)
Name
Description
Default
(Range)
n4-74
(1B8E)
Limit of Flux Loop
Sets the control level for flux loop control output.
250%
(100 - 500%)
If the torque is not sufficient because of 100% or more loads, increase the setting value in 20% increments. If the
setting is too high, overexcitation could occur and overheat the motor.
◆
n5: Feed Forward Control
Feed forward control increases the responsiveness of acceleration and deceleration as specified by the speed
reference.
Increase
C5-01 and C5-03 [ASR Proportional Gain]
to apply feed forward control to machines that have low rigidity
and are possible to have hunting and vibration or to machines that have a large quantity of inertia. When you use this
function in CLV control, it also helps prevent overshoot. Refer to
. Refer to
for more
information about parameters related to feed forward control.
Set
A1-02 [Control Method Selection]
to one of these values to enable feed forward control:
•
3: Closed Loop Vector Control
•
4: Advanced OpenLoop Vector Control
•
6: PM Advanced Open Loop Vector
•
7: PM Closed Loop Vector Control
Note:
•
You cannot use feed forward control to increase responsiveness in applications where you apply loads externally during run at constant
speed.
•
When you use the Droop control function, set
n5-01 = 0 [Feed Forward Control Selection = Disabled]
.
•
You cannot use feed forward control with motor 2.
Figure 12.144 Suppress Overshooting with Feed Forward Control
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA80U4720ABM
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...