352
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Code
Name
Causes
Possible Solutions
oPE33
Digital Output Selection Error
These two parameters are set at the same time:
•
H2-60 ≠ F [Term M1-M2 Secondary Function ≠
Not Used]
•
H2-01 = 1xx [Term M1-M2 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
•
H2-63 ≠ F [Term M3-M4 Secondary Function ≠
Not Used]
•
H2-02 = 1xx [Term M3-M4 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
•
H2-66 ≠ F [Term M5-M6 Secondary Function ≠
Not Used]
•
H2-03 = 1xx [Term M5-M6 Function Selection =
Inverse output of xx]
Clear the
H2-01 to H2-03 = 1xx [Inverse output of xx]
settings.
Note:
It is not possible to set
H2-01 to H2-03 = 1xx [Inverse output of
xx]
when using output functions for logic operations (
H2-60,
H2-63, H2-66 ≠ F
).
These parameter pairs are set incorrectly:
•
H2-21 [Comparator 1 Lower Limit]
>
H2-22
[Comparator 1 Upper Limit]
•
H2-27 [Comparator 2 Lower Limit]
>
H2-28
[Comparator 2 Upper Limit]
•
Set parameters
H2-21
≤
H2-22
.
•
Set parameters
H2-27
≤
H2-28
.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...