826
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Note:
•
Refer to H1-xx
“
MFDI setting values
”
for the setting values of the MFDI.
•
You cannot set
0 [3-Wire Sequence]
or
20 to 2F [External fault]
in
H1-40
to
H1-42
.
•
When you will not use
H1-40
to
H1-42
, set them to
F [Through Mode]
.
•
You cannot use MFDI for digital input option D1-A3 at the same time as function selection for MEMOBUS/Modbus MFDI 1 to 3.
■
H1-40: Mbus Reg 15C0h bit0 Input Func
No.
(Hex.)
Name
Description
Default
(Range)
H1-40
(0B54)
Mbus Reg 15C0h bit0 Input
Func
Selects MFDI function assigned to
bit 0
of the MEMOBUS register
15C0 (Hex.)
.
F
(1 - 19F)
■
H1-41: Mbus Reg 15C0h bit1 Input Func
No.
(Hex.)
Name
Description
Default
(Range)
H1-41
(0B55)
Mbus Reg 15C0h bit1 Input
Func
Selects MFDI function assigned to
bit 1
of the MEMOBUS register
15C0 (Hex.)
.
F
(1 - 19F)
■
H1-42: Mbus Reg 15C0h bit2 Input Func
No.
(Hex.)
Name
Description
Default
(Range)
H1-42
(0B56)
Mbus Reg 15C0h bit2 Input
Func
Selects MFDI function assigned to
bit 2
of the MEMOBUS register
15C0 (Hex.)
.
F
(1 - 19F)
◆
Multi-Function Digital Input Setting Values
Selects a function set with
H1-01 to H1-08
.
■
0: 3-Wire Sequence
Setting Value
Function
Description
0
3-Wire Sequence
Sets the direction of motor rotation for 3-wire sequence.
If the 3-wire sequence is set to a terminal that is not MFDI terminals S1 and S2, these terminals will be the input
terminals for Forward run/Reverse run command. The drive will automatically set terminal S1 to Run command
(RUN) and terminal S2 to Stop command (STOP).
When terminal S1 (Run command) activates for 1 ms minimum, the drive rotates the motor. When terminal S2 (Stop
command) deactivates, the drive stops. When terminal Sx that is set in 3-wire sequence deactivates, the drive operates
in the forward direction, and when it activates, the drive operates in the reverse direction.
WARNING!
Sudden Movement Hazard. Set the MFDI parameters before you close control circuit switches. Incorrect Run/Stop
circuit sequence settings can cause serious injury or death from moving equipment.
WARNING!
Sudden Movement Hazard. When you use a 3-Wire sequence, set A1-03 = 3330 [Initialize Parameters = 3-Wire
Initialization] and make sure that b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command] (default). If you do
not correctly set the drive parameters for 3-Wire operation before you energize the drive, the motor can suddenly rotate when you
energize the drive.
Figure 12.77 3-Wire Sequence Wiring Example
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...