166
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
◆
Save a Backup of Parameters
You can save a backup of the drive parameters to the keypad. The keypad can store parameter setting values for a
maximum of four drives in different storage areas. Parameter setting backups can save time when you set parameters
after you replace a drive. If you set up more than one drive, you can copy the parameter settings from a drive that
completed a test run to the other drives.
Note:
•
Stop the motor before you back up parameters.
•
While you back up parameters, the drive will not accept Run commands.
•
The DriveWorksEZ PC software password is necessary to back up
qx-xx [DriveWorksEZ Parameters]
and
rx-xx [DWEZ Connection
Parameters]
. If you enter an incorrect password, the drive detects
PWEr [DWEZ Password Missmatch]
.
1.
Push
(Home) to show the HOME screen.
Note:
• When the drive is in HOME Mode, the screen shows [Home] in the upper right-hand corner of the screen.
• If the screen does not show [Home] for
, push
(Back), and then push
to show [Home].
2.
Push
(Menu).
3.
Push
or
to select [Parameter Backup/Restore], then push
.
4.
Push
or
to select the items to back up, then push
.
5.
Push
or
to select [Backup (drive → keypad)], then push
.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...