WARNING!
Electrical Shock Hazard. After the drive blows a fuse or trips a GFCI, do not immediately energize the drive or operate
peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators are OFF. Then
check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of the problem, contact
Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you operate the drive or peripheral
devices, it can cause serious injury or death.
Table 5.2 Factory-Recommended Branch Circuit Protection (200 V Class)
Drive Model
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
2004
FWH-45B
2006
FWH-45B
2008
FWH-45B
2010
FWH-45B
2012
FWH-50B
2018
FWH-80B
2021
FWH-80B
2030
FWH-125B
2042
FWH-150B
2056
FWH-200B
2070
FWH-225A
Drive Model
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
2082
FWH-225A
FWH-250A
2110
FWH-225A
FWH-250A
2138
FWH-275A
FWH-300A
2169
FWH-275A
FWH-350A
2211
FWH-325A
FWH-450A
2257
FWH-600A
2313
FWH-800A
2360
FWH-1000A
2415
FWH-1000A
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
Table 5.3 Factory-Recommended Branch Circuit Protection (400 V Class)
Drive Model
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
4002
FWH-50B
4004
FWH-50B
4005
FWH-50B
4007
FWH-60B
4009
FWH-60B
4012
FWH-60B
4018
FWH-80B
4023
FWH-90B
4031
FWH-150B
4038
FWH-200B
4044
FWH-200B
4060
FWH-225A
4075
FWH-250A
4089
FWH-275A
Drive Model
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
4103
FWH-275A
4140
FWH-300A
4168
FWH-325A
FWH-400A
4208
FWH-500A
4250
FWH-600A
4302
FWH-700A
4371
FWH-800A
4414
FWH-1000A
4477
FWH-1200A
4568
FWH-1200A
4605
FWH-1400A
4720
FWH-1400A
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
■
CE Standards Compliance for DC Power Supply Input
To comply with CE Standards, install a fuse for the DC power supply input.
shows a wiring example for a DC power supply that has two drives connected in parallel.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...