Figure 5.3 Wiring Example for DC Power Supply Input
WARNING!
Electrical Shock Hazard. Do not ground the main circuit bus. Incorrect wiring can cause serious injury or death.
Note:
•
Install a fuse for each drive when operating more than one drive. If one fuse blows, replace all fuses.
•
Install the external filter (system) to comply with the EMC Directive.
Refer to
and
for the recommended fuses.
Table 5.4 Recommended Fuse (Three-Phase 200 V Class)
Drive Model
Fuse
Manufacturer: Bussmann
Model
Quantity
2004
FWH-45B
2
2006
FWH-45B
2
2008
FWH-45B
2
2010
FWH-45B
2
2012
FWH-50B
2
2018
FWH-80B
2
2021
FWH-80B
2
2030
FWH-125B
2
2042
FWH-150B
2
2056
FWH-200B
2
2070
FWH-250A
2
2082
FWH-250A
2
2110
FWH-250A
2
2138
FWH-300A
2
2169
FWH-350A
2
2211
FWH-450A
2
2257
FWH-600A
2
2313
FWH-800A
FWH-1000A
2
2360
FWH-1000A
2
2415
FWH-1000A
2
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...