ON : The Run command turns on and the magnetic contactor on the input side turns on.
OFF : The Run command turns off and the drive stops operating. Then, the magnetic contactor on
the input side turns off after the time set with
b8-51 [Standby Mode Wait Time]
elapses.
■
66: Comparator1
Setting Value
Function
Description
66
Comparator1
The terminal activates if the monitor value set with
H2-20 [Comparator 1 Monitor Selection]
is in range of the values of
H2-21
[Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit]
for the time set in
H2-24 [Comparator 1 On-Delay Time]
.
A - H2-24
[Comparator 1 On-Delay Time]
B - H2-25
[Comparator 1 Off-Delay Time]
Figure 12.101 Comparator 1 Output Time Chart
Note:
The drive compares the monitors set with
H2-20
as absolute values.
■
67: Comparator2
Setting Value
Function
Description
67
Comparator2
The terminal activates if the monitor value set with
H2-26 [Comparator 2 Monitor Selection]
is not in the range of the values of
H2-
27 [Comparator 2 Lower Limit]
and
H2-28 [Comparator 2 Upper Limit]
for the time set in
H2-30 [Comparator 2 On-Delay Time]
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...