Figure 3.37 Tightening Torque Display Location (Reverse side of Front Cover)
Figure 3.38 Tightening Torque Display Location (Lower Front Side of Front Cover)
■
Control Circuit Wire Gauges and Tightening Torques
Use the tables in this section to select the correct wires. Use shielded wire to wire the control circuit terminal block.
Use crimp ferrules on the wire ends to make the wiring procedure easier and more reliable.
Table 3.12 Control Circuit Wire Gauges and Tightening Torques
Terminal Block
Terminal
Screw Size
Tightening
Torque
N
∙
m (in
∙
lb)
Bare Wire
Crimp Ferrule
Recommended
Gauge
mm
2
(AWG)
Applicable
Gauge
mm
2
(AWG)
Recommended
Gauge
mm
2
(AWG)
Applicable
Gauge
mm
2
(AWG)
TB1
S1 - S8, SN, SC, SP
M3
0.5 - 0.6
(4.4 - 5.3)
0.75
(18)
•
Stranded wire
0.2 - 1.0
(24 - 16)
•
Solid wire
0.2 - 1.5
(24 - 16)
0.5
(20)
0.25 - 0.5
(24 - 20)
TB2
M1 - M6, MA, MB, MC
TB3
+V, AC, -V, A1, A2, A3, FM, AM,
AC, MP, RP, AC
TB4
E (G), SN, HC, H1, H2, PS, AC, D
+, D-
TB5
E (G)
M3.5
0.5 - 1.0
(4.4 - 8.9)
0.5 - 2
(20 - 14)
1.25
(12)
-
-
Crimp Ferrules
Attach an insulated sleeve when you use crimp ferrules. Refer to
for the recommended external
dimensions and model numbers of crimp ferrules.
Use the CRIMPFOX 6, a crimping tool made by PHOENIX CONTACT.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...