282
YASKAWA
TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
■
Single-Phase 200 V Class
Table 10.9 Factory-Recommended Branch Circuit Protection: Single-Phase 200 V Class
Drive Model
Maximum Applicable Motor
Output
kW (HP)
Time Delay
Fuse
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
ND
HD
Class J, T, and
CC Fuse
Rated Current
A
Model
Input Rated
Current
A
B001
0.18 (1/6)
0.1 (1/6)
3
FWH-25A14F
25
B002
0.37 (1/4)
0.25 (1/4)
6
FWH-25A14F
25
B004
0.75 (3/4)
0.55 (1/2)
10
FWH-60B
60
B006
1.1 (1.5)
1.1 (1)
15
FWH-80B
80
B010
2.2 (3)
1.5 (2)
25
FWH-100B
100
B012
3.0 (3)
2.2 (3)
30
FWH-125B
125
B018
-
4.0 (5)
-
FWH-150B
150
■
Three-Phase 400 V Class
Table 10.10 Factory-Recommended Branch Circuit Protection: Three-Phase 400 V Class
Drive Model
Maximum Applicable Motor
Output
kW (HP)
Time Delay
Fuse
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
ND
HD
Class J, CC,
and T Fuse
Rated Current
A
Model
Input Rated
Current
A
4001
0.37 (1/2)
0.37 (1/2)
3
FWH-40B
40
4002
0.75 (1)
0.55 (3/4)
6
FWH-40B
40
4004
1.5 (2)
1.1 (2)
10
FWH-50B
50
4005
2.2 (3)
1.5 (3)
10
FWH-70B
70
4007
3.0 (4)
2.2 (3)
15
FWH-70B
70
4009
4.0 (5)
3.0 (4)
20
FWH-90B
90
4012
5.5 (7.5)
4.0 (5)
25
FWH-90B
90
4018
7.5 (10)
5.5 (10)
-
FWH-80B
80
4023
11.0 (15)
7.5 (10)
-
FWH-100B
100
4031
15.0 (20)
11.0 (15)
-
FWH-125B
125
4038
18.5 (25)
15.0 (20)
-
FWH-175B
175