YASKAWA
TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
303
■
Three-Phase 400 V Class
Model
Terminal
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Wire
Stripping
Length
mm
Terminal Screw
Tightening
Torque
N
∙
m (in
∙
lb)
Size
Shape
4001
R/L1, S/L2, T/L3
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
14 - 10
-
M4
1.2 - 1.5
(10.6 - 13.3)
4002
R/L1, S/L2, T/L3
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
14 - 10
-
M4
1.2 - 1.5
(10.6 - 13.3)
4004
R/L1, S/L2, T/L3
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
14
14 - 12
8
M3
0.5 - 0.6
(4.4 - 5.3)
14 - 10
-
M4
1.2 - 1.5
(10.6 - 13.3)