YASKAWA
TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
307
Model
Terminal
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Wire
Stripping
Length
mm
Terminal Screw
Tightening
Torque
N
∙
m (in
∙
lb)
Size
Shape
4044
R/L1, S/L2, T/L3
4
10 - 2
18
M5
•
≤ AWG 10
2.3 - 2.5
(19.8 - 22)
•
AWG 8 ≤
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3
6
12 - 4
18
M5
•
≤ AWG 10
2.3 - 2.5
(19.8 - 22)
•
AWG 8 ≤
4.1 - 4.5
(36 - 40)
-, +1, +2
2
8 - 2
18
M5
4.1 - 4.5
(36 - 40)
B1, B2
8
12 - 6
10
M4
1.5 - 1.7
(13.5 - 15)
6
10 - 6
-
M6
5.4 - 6.0
(47.8 - 53.1)
4060
R/L1, S/L2, T/L3
2
8 - 2
18
M5
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3
4
10 - 2
18
M5
•
≤ AWG 10
2.3 - 2.5
(19.8 - 22)
•
AWG 8 ≤
4.1 - 4.5
(36 - 40)
-, +1, +2
2
6 - 2
18
M5
4.1 - 4.5
(36 - 40)
B1, B2
8
12 - 6
10
M4
1.5 - 1.7
(13.5 - 15)
6
10 - 6
-
M6
5.4 - 6.0
(47.8 - 53.1)
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-
loop crimp terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of
10 mm
2
(copper wire).
•
8-4NS from JST Mfg. Co., Ltd.
•
R8-4S from NICHIFU Co.,Ltd.