YASKAWA
TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
17
Sym
bol
Name
Function
M
DWEZ LED
Illuminated: The drive is In DriveWorksEZ operation.
N
RJ-45 Connector
Connects to the drive. Use an RJ-45 8-pin straight through UTP CAT5e extension cable to
install the keypad in a different location than the drive.
WARNING
Sudden Movement Hazard. If you change the control source when b1-07 = 1 [LOCAL/
REMOTE Run Selection = Accept Existing RUN Command], the drive can start suddenly. Before you change the
control source, remove all personnel from the area around the drive, motor, and load. Sudden starts can cause
serious injury or death.
◆
Installation
WARNING
Fire Hazard. Do not put flammable or combustible materials on top of the drive and do not
install the drive near flammable or combustible materials. Attach the drive to metal or other noncombustible
material. Flammable and combustible materials can start a fire and cause serious injury or death.
CAUTION
Crush Hazard. Tighten terminal cover screws and hold the case safely when you move the
drive. If the drive or covers fall, it can cause moderate injury.
NOTICE
Install the drive as specified by EMC Guidelines. If you do not obey the EMC Guidelines, it
can cause incorrect operation and damage to electrical devices.
NOTICE
Do not let unwanted objects, for example metal shavings or wire clippings, fall into the
drive during drive installation. Put a temporary cover over the drive during installation. Remove the temporary
cover before start-up. Unwanted objects inside of the drive can cause damage to the drive.
NOTICE
Obey correct electrostatic discharge (ESD) procedures when you touch the drive.
Incorrect ESD procedures can cause damage to the drive circuitry.
Note:
Do not put drive peripheral devices, transformers, or other electronics near the drive. Shield the drive from electrical
interference if components must be near the drive. Components near the drive can cause incorrect drive operation from
electrical interference.
■
Installation Environment
The installation environment is important for the lifespan of the product and to make sure that
the drive performance is correct. Make sure that the installation environment agrees with these
specifications.
Environment
Conditions
Area of Use
Indoors
Power Supply
Overvoltage Category III
Ambient
Temperature
Setting
IP20/UL Open Type: -10°C to +50 °C (14 °F to 122 °F)
IP20/UL Type1: -10 °C to +40 °C (14 °F to 104 °F)
•
Drive reliability is better in environments that do not have wide temperature fluctuations.
•
When installing the drive in an enclosure, use a cooling fan or air conditioner to keep the internal
air temperature in the permitted range.
•
Do not let the drive freeze.
Humidity
95%RH or less
Do not let condensation form on the drive.
Storage
Temperature