Mode
l
Terminal
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Wire
Stripping
Length
mm
Terminal Screw
Tightening
Torque
N
∙
m (in
∙
lb)
Size
Shape
2082
R/L1, S/L2, T/L3
35
10 - 50
20
M6
5 - 5.5
(45 - 49)
U/T1, V/T2, W/T3
25
10 - 35
20
M6
5 - 5.5
(45 - 49)
-, +1, +2
50
16 - 70
20
M6
5 - 5.5
(45 - 49)
B1, B2
16
4 - 16
10
M4
1.5 - 1.7
(13.5 - 15)
16
10 - 25
-
M6
5.4 - 6.0
(47.8 - 53.1)
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-
loop crimp terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of
10 mm
2
(copper wire).
•
8-4NS from JST Mfg. Co., Ltd.
•