10 General Class Objects
YASKAWA ELECTRIC
SIEP C730600 58A 1000-Series Option SI-EN3 Technical Manual
EN 43
Note:
“Get Attributes All” Service shall report in attribute ascending order.
Ethernet Link Object 246 (Class 0xF6)
Services Supported
Attributes Supported
Note:
“Get Attributes All” Service shall report in attribute ascending order.
1
3
Configuration Control
Bits 0-3 = Startup Configuration
0: NVRAM
1: BOOTP
2: DHCP
3: Reserved
Bit 4 =DNS Enabled (not supported)
Bits 5-31 = Reserved
O
O
DWord
–
–
1
4
Physical Link
Struct of:
Path Size: Word
Path: EPATH
O
–
Struct
–
02H 00H 20H
F6H 24H 01H
1
5
Interface Configuration
Struct of:
IP Address = Long
Subnet Mask = Long
Gateway Address = Long
Name Server1 = Long
Name Server2 = Long
Domain Name = STRING
O
O
Struct
–
–
1
6
Host Name
Host Name
O
O
STRING 64 Characters
Null
Service Code No. (H)
Service Name
01
Get Attribute All
0E
Get Attribute Single
10
Set Attribute Single
Instance
ID
Attribute
Name
Name
Get Set
Size
Range
Default
0
1
Object Software Revision
Revision number of the Ethernet Link
Object
O
–
Word
–
3
1
1
Interface Speed
Interface speed currently in use
O
–
UDINT
–
–
1
2
Interface Flags
Bit 0 = Link Status
Bit 1 = Duplex (0: Half/1: Full)
Bits 2-4 = Negotiation Status
0: In progress
1: Auto-negotiate failed
2: Speed found, duplex not found
3: Successful
4: Not attempted
Bit 5 = Manual Setting requires restart
Bit 6 = Local hardware fault
Bits 7-31 = Reserved
O
–
DWord
–
–
1
3
Physical Address (MAC)
MAC address
O
–
Array of 6
Bytes
–
–
1
6
Interface Control
Struct of:
Control Bits: Word
Bit 0 = Auto-negotiate
Bit 1 = Forced Duplex Mode
Bits 2-15 = Reserved
Forced Int Speed: Word
–
O
Struct
–
–
Instance
ID
Attribute
Name
Description
Get Set
Size
Range
Default