6 Related Drive Parameters
EN 18
YASKAWA ELECTRIC
SIEP C730600 58A 1000-Series Option SI-EN3 Technical Manual
Table 7 Option Monitors
F7-23 to
F7-32
(3FB to
404)
Dynamic Output Assembly
Parameters
Parameters used in Output Assembly 116. Each parameter contains a
MEMOBUS/Modbus address. The value received for Output Assembly
116 will be written to this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value received for
Output Assembly 116 will not be written to any MEMOBUS/Modbus
register.
Default: 0
F7-33 to
F7-42
(405 to
40E)
Dynamic Input Assembly
Parameters
Parameters used in Input Assembly 166. Each parameter contains a
MEMOBUS/Modbus address. The value sent for Input Assembly 166 will
be read from this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value sent for
Input Assembly 166 is not defined by the user, therefore the option default
register value will be returned.
Refer to Input Assemblies (Drive Produces) on page 27
for definitions of
the default MEMOBUS/Modbus registers.
Default: 0
<1> To start and stop the drive with the EtherNet/IP master device using serial communications, set b1-02 to 3 or set the “Net Control” bit in the
assemblies or Control Supervisor Object. To control the drive frequency reference of the drive via the master device, set b1-01 to 3 or set the
Net Reference bit in the assemblies or AC/DC Object.
<2> If F6-01 is set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as installing an emergency stop
switch.
<3> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01 determines whether the value is read as the
Torque Limit value (d5-01 = 0) or read as the Torque Reference value (d5-01 = 1). In CLV/PM, this value is read as the Torque Limit.
<4> The setting specifies that the Torque Reference or Torque Limit is to be provided via network communications (F6-06 = 1). The motor may
rotate if no torque reference or Torque Limit is supplied from the PLC.
<5> Cycle power for setting changes to take effect.
<6> If F7-13 is set to 0, then all IP Addresses (F7-01 to F7-04) must be unique.
<7> Set F7-01 to F7-12 when F7-13 is set to 0.
<8> Set F7-15 when F7-14 is set to 0 or 2.
No.
Name
Description
Value Range
U6-80 to U6-83
Online IP Address
IP Address currently available; U6-80 is the most significant octet
0 to 255
U6-84 to U6-87
Online Subnet
Subnet currently available; U6-84 is the most significant octet
0 to 255
U6-88 to U6-91
Online Gateway
Gateway currently available; U6-88 is the most significant octet
0 to 255
U6-92
Online Speed
Link Speed
10: 10 Mbps
100: 100 Mbps
U6-93
Online Duplex
Duplex Setting
0: Half, 1: Full
U6-98
First Fault
First Option Fault
–
U6-99
Current Fault
Current Option Fault
–
No.
(Addr.
Hex)
Name
Description
Values