Parameter name
Default value
Level
Description
P6-21:Relay output 3 and 4
0
3
Configures when relay output is open or closed.
One digit for each relay
Relay 3: Position 1
Relay 4: Position 2
• 0: Enable
• 1: Leakage alarm
• 2: Pump over temp alarm
• 3: High level alarm (Dig)
• 4: Sensor error
• 5: High level alarm (An)
• 6: Trip
• 7: A-Alarm
• 8: B-Alarm
• 9: Pump running
Example: P6-21 = 48
Relay 3 = Sensor error alarm
Relay 4 = B-alarm, sum
For more information, see
42).
P8-01:Stir interval duration
0
2
Configures the time of inactivity in standby mode that triggers the
maintenance run function.
For more information, see
Table 10: Read-only parameters
Parameter name
Level
Description
P0-01:Analog input 1 value
2
Displays the signal level that is applied to analog input 1 (Terminal 6)
after scaling and offsets have been applied.
P0-02:Analog input 2 value
2
Displays the signal level that is applied to analog input 2 (Terminal 10)
after scaling and offsets have been applied.
P0-03:Digital input status
2
Displays the status of the digital inputs.
P0-11:Motor voltage
2
Displays the instantaneous output voltage from the drive to the motor.
P0-13:Trip log
2
Displays the last four fault codes for the drive.
P0-23:Time heatsink > 85C
2
Displays two entries: First display shows hours. Second display shows
minutes and seconds. Displays the amount of time in hours and
minutes that the drive has operated during its lifetime with a heatsink
temperature in excess of 80°C (176°F). The drive uses this parameter
for various internal protection and monitoring functions.
P0-24:Time ambient > 80C
2
Displays two entries: First display shows hours. Second display shows
minutes and seconds. Displays the amount of time in hours and
minutes that the drive has operated during its lifetime with an
ambient temperature in excess of 80°C (176°F). The drive uses this
parameter for various internal protection and monitoring functions.
P0-26:kWh meter
2
Displays two entries: First display shows meters. Second display shows
the amount of energy that the drive consume in kWh. When the value
reaches 1000, it is reset back to 0.0, and the value of P0-27:MWh
meter (MWh meter) is increased.
P0-27:MWh meter
2
Displays two entries: First display shows meters. Second display shows
the amount of energy that is consumed by the drive in MWh.
P0-28:Software version
2
Displays the firmware software version of the drive: Four entry display:
First display = I/O version, second display = I/O checksum, third
display = DSP version, fourth display = DSP checksum.
Technical Reference
56