Data
Description
Maximum switching current
6 A (250 V AC) / 5 A (30 V DC)
Ambient temperature
-10ºC – +50ºC
International Protection Marking
IP20
UL standard
UL94V-0
Terminal torque value
0.5 Nm (4.5 Ib in)
Communication
The drive and the sump status and health can be monitored remotely. There are some
parameters that are suitable for remote control. The drive is not designed to have external
equipment, or let external equipment control the activities in the sump. Examples of
parameters that are suitable to monitor remotely are:
• water level
• frequency
• current consumption
• drive temperature
• trip log
• alarm log
Example of parameters that are suitable for remote control are:
• start level
• stop level
• maximum frequency
• minimum frequency
The drive communicates natively using Modbus RTU. If a SCADA system requires another
protocol, then a gateway is needed. The gateway Flygt MyConnect is preconfigured to let
the drive communicate with the SCADA system Aquaview 7 over Aquacom protocol, or
Modbus RTU with other SCADA systems. APP700 and MultiSmart are products that can
also be used to communicate with the drive from SCADA systems.
The data plate
1
3
5
4
2
WS003655
1.
Model number
2.
Input values, voltage, frequency, number of phases, current
3.
Output values, voltage, frequency, number of phases, current
4.
Serial number
5.
UL-approval
Product Description
10
SRC 311 - SmartRun
™
Installation, Operation, and Maintenance Manual