Torque values
Control terminal
Torque value 0.8 Nm (7.00 lb in)
Power terminal
Drive size
Nm
lb in
2
1.0
8.85
3
1.0
8.85
4
4.0
3.00
5
15.0
11.10
6
20.0
15.00
Optional modules
Torque value 0.5 Nm (4.50 lb in)
Install the system
Requirements
• The mechanical installation of pumps, switch, and sensors is completed.
• The pumps that are installed must be equipped with FLS, thermal contacts. If no FLS is
used the P1-22:Leakage alarm setup parameter must be set to 0: Off.
• The pumps must be installed with screened cables.
• Do not install any type of automatic switchgear between the drive and the motor.
Install a two pump system
WS008323
1
2
1. Prepare the drives cable throughlet.
Electrical Installation
SRC 311 - SmartRun
™
Installation, Operation, and Maintenance Manual
21