0.62 m
LED display messages, IP20
This information do not apply to the IP55 and IP66 since they are equipped with OLED
displays.
Display
Status
Drive mains power is applied, but no Enable or Run
signal is applied.
Motor Autotune in progress.
Drive running, display shows output frequency (Hz).
Drive running, display shows motor current (Amps).
Drive Running, display shows motor power (kW).
Drive Running, display shows customer selected units,
see P2-21:Display scaling factor, P2-22:Display scaling
source.
Drive mains power not present, external 24 V control
power supply present only.
Output power hardware enable circuit open. External
links are required to the STO inputs (terminals 12 and 13)
Parameters reset to factory default settings.
Parameters reset to User default settings.
(page 47).
Start-up guidelines
The drive is loaded with pre-set default values that work well for wastewater applications.
To set up the drive to specific pump station conditions, review in sequence and where
applicable adjust the parameters. For more information, see
(page
52).
1. Complete the product installation according to the instructions in
(page 21).
2. Ascertain that the sensor is placed properly in the sump, also learn the correct sensor
scaling from the sensor label.
3. Energize the drive.
4. Press the navigate button.
5. Navigate to the desired parameter.
Open applicable parameter
Action
P1-08:Motor rated current
Set the rated current of the pump motor.
P1-15:Start level
Set the sump level where the pump starts pumping.