Software parameters
Table 9: Changeable parameters
Parameter name
Default value
Level
Description
P1-01:Maximum speed limit
Varies
1
Maximum speed limit
P1-02:Minimum speed limit
30.0 Hz
1
Minimum speed limit
P1-03:Acceleration ramp time
1.0 s
1
Acceleration ramp time
P1-04:Deceleration ramp time
10.0 s
1
Deceleration ramp time
P1-06:Motor energy optimiser
0: disable
1
Configures the motor energy optimizer. When the energy optimization
is enabled, the motor voltage dynamically varies according to load. This
function leads to reduced power consumption during low load
operation.
P1-07:Motor rated voltage
Varies
1
Configure the rated voltage of the motor.
The value is found on data plate on the motor.
P1-08:Motor rated current
Varies
1
Configures the rated current of the motor.
The value is found on data plate on the motor.
P1-09:Motor rated frequency
Varies
1
Configures the frequency of the motor.
The value is found on data plate on the motor.
P1-14:Extended menu access
0
1
Access codes:
0: Allows access to Parameter Group 1 only
299: Allows access to medium parameters
505: Allows access to advanced parameters
P1-15:Start level
Varies
1
Configures the start level of the pump in m or ft.
For more information, see
Start and stop levels (default
(page 35).
P1-16:Stop level
Varies
1
Configures the stop level of the pump in m or ft.
The distance between the start level and the stop level must be <10%
of the sensors measuring range. For example, a level sensor with the
range 0-5 m (0-16.4 ft) must have the start level 0.5 m (0-1.64 ft) above
the stop level.
For more information, see
Start and stop levels (default
(page 35).
P1-17:Pump cleaning settings
1
1
Configures the cleaning function.
• 0: Off
• 1: On
• 2: On & 2h
• 3: On & 5h
• 4: On & 10h
• 5: On & 20h
P1-18:Energy frequency
550
1
Displays the most energy efficient frequency that the energy minimizer
function calculates.
For more information, see
(page 37).
P1-19:Alarm state
0
1
Active alarms shown as a number
For more information, see
(page 46).
P1-20:OnOff
0
1
On / Off emulates pressing the start and stop buttons on the keypad,
but does not reset active alarms.
P1-21:Sensor max level
Varies
1
Configures the scale factor for the level sensors range. Sensor range for
50 Hz is in cm and for 60 Hz in a 100th of a foot.
Technical Reference
52
SRC 311 - SmartRun
™