Parameter name
Default value
Level
Description
P1-22:Leakage alarm setup
4
1
Configure the leakage alarm. If no FLS is connected, then turn off the
alarm. Setting FLS=Off will automatically configure the drive for the
thermal contact triggering of the over temperature alarm. When over
temperature alarm is active, hand-mode is not available.
• 0: Off
• 1: A alarm, auto reset
• 2: B alarm, auto reset
• 3: A alarm, stop pump
• 4: A alarm
• 5: B alarm
Alarm and monitoring functions
(page 45).
P1-23:Hi lvl alarm setup-Dig
4
1
Configures high-level alarm from the digital level switch.
• 0: Off
• 1: A alarm, auto reset
• 2: B alarm, auto reset
• 3: A alarm, stop pump
• 4: A alarm
• 5: B alarm
P1-24:Hi lvl alarm set. -Analog
4
1
Configures high-level alarm from the analog level sensor.
• 0: Off
• 1: A alarm, auto reset
• 2: B alarm, auto reset
• 3: A alarm, stop pump
• 4: A alarm
• 5: B alarm
P1-25:Sensor error alarm setup
Configures the sensor error alarm for the analog level sensor.
• 0: Off
• 1: A alarm, auto reset
• 2: B alarm, auto reset
• 3: A alarm, stop pump
• 4: A alarm
• 5: B alarm
P2-09:Skip freq centre point
0.0 Hz
2
Configures the center point of the skip frequency band. The parameters
define the width of the skip frequency band:
• Lower limit = P2-09 - P2-10/2
• Upper limit = P2-09 + P2-10/2
All skip frequency bands that are defined for forward speeds are
mirrored for negative speeds. The energy function is impacted by the
skip frequency function and cannot search for an energy frequency in
the forbidden band. If the band is set wider than 1 Hz, then the energy
function does not search for frequencies below the skip frequency band.
P2-10:Skip frequency band
0.0 Hz
2
Configures the width of the skip frequency band. The parameters define
the width of the skip frequency band: Lower limit = P2-09 -
P2-10/2Upper limit = P2-09 + P2-10/2 All skip frequency bands that
are defined for forward speeds are mirrored for negative speeds.
Technical Reference
SRC 311 - SmartRun
™
Installation, Operation, and Maintenance Manual
53