Optional module functions
External relay
The P6-21:Relay output 3 and 4 parameter controls the function for relay 3 and 4. Relay 5
is always closed when the drive runs.
External I/O controller
To put the drive in external I/O control mode, close extended digital input 3. In external
I/O control mode, the drive does not respond to the keypad buttons On, Off, Hand or
Auto. The drive can now be put in two modes. By enabling extended digital input 1, the
drive goes into auto mode and starts when the start level is reached. Auto mode
corresponds to pushing the buttons auto and then On.
By enabling extended digital input 2, the drive starts at maximum speed. This setting
corresponds to pushing the buttons Hand and then On.
If both extended digital input 1 and 2 are opened or closed, then the drive does not start.
To switch back to the drive keypad control, open extended digital input 3.
The module has a built-in relay that is configured as relay 3 in the P6-21:Relay output 3
and 4 parameter.
Ext block
+24 V
Alarm reset
High
level
in
Gnd
T2 in
Lvl signal
out
Gnd Lvl signal
in
Active pump Inhibit in
Inhibit out
+ 10V
1 2 3 4
5 6 7 8
9 10 11 12 13
Control Terminal
DI 3
DI 2
Not in
use
Relay
comm
Relay
op con
2 3 4 5 6
H-0-A interface
1
DI
1
WS008804A
Unlock the extended parameters set
The drive contains three levels of parameters. Two of the levels require a password.
Level
Password
Description
1
0
Parameters for basic drive and
process settings.
2
299
Parameters for medium settings.
3
505
Parameters for advanced settings.
1. Hold down the Navigation button for more than 2 seconds.
2. Use the Up and Down button to navigate to the P1-14:Extended menu access
parameter.
3. Enter the password.
Use the Up and Down button to edit the value.
4. Change the settings value to fit the specific conditions of the pump station.
When the required settings are changed, make sure that the parameters are locked again.
Follow the same procedure but change the password to 0.
Factory reset the drive
Resetting the drive to the factory state reverses all the settings to the state they were when
the drive was delivered.
System Setup and Operation
42
SRC 311 - SmartRun
™
Installation, Operation, and Maintenance Manual