51
5-5-6. Speed coincidence checking (/V-CMP)
When motor speed is equal to the command speed, servo outputs speed coincidence signal
(V-CMP).
Parameter
Signal
Default
Meaning
Modify
P5-29
/V-CMP
n.0000
Need to
distribute
Range: 0000-0013. Distribute to output
terminal through P5-29. When it set to
0002, it means output from SO2.
5-5-7. Torque limit
5-5-7-1. Internal torque limit (output torque max value limit)
The function is to limit the max output torque by parameters.
P4-02
Forward torque limit
Unit
Default
Range
Suitable mode
Modify
Effective
1%
300
0~300
All modes
Servo OFF
Immediately
P4-03
Reverse torque limit
Unit
Default
Range
Suitable mode
Modify
Effective
1%
300
0~300
All modes
Servo OFF
Immediately
1. This parameter is always effective, if this parameter value is less than external torque limit value, the
final limit value is this parameter.
2. The unit is percent of the motor rated torque; the default value is 300%. The real output torque is
different for each type.
5-5-7-2. External torque limit (via input signal)
This function is used in machine motion or timing torque limit. For example: press stop
action or robot workpiece protection.
Zero clamp will act when meets the following conditions:
Speed control (submode 3 or 4)
Set ON /ZCLAMP
Speed command value is less than the value of P5-01
P5-03
Speed coincidence signal width
Unit
Default
Range
Suitable mode
Modify
Effective
rpm
10
1~250
3, 4, 7
Servo OFF
Immediately
If the difference between motor speed and command speed is less than the value of P5-03, servo
outputs /V-CMP signal.
Zero clamp
voltage
V-REF speed command
ON
ON
OFF
Zero clamp acts
/ZCLAMP input