9
Servo Drive Orientation
Install the servo drive perpendicular to the wall so the front panel containing connectors
faces outward.
Cooling
As shown in the figure above, allow sufficient space around each servo drive for cooling
by cooling fans or natural convection.
Side-by-side Installation
When install servo drives side by side as shown in the figure above, make at least 10mm
between and at least 50mm above and below each servo drive. Install cooling fans above
the servo drives to avoid excessive temperature rise and to maintain even temperature
inside the control panel.
Environmental Conditions in the Control Panel
Ambient Temperature: 0~50
℃
Humidity: 90%RH or less
Vibration: 4.9m/s
2
Condensation and Freezing: None
Ambient Temperature for Long-term Reliability: 50°C maximum