© 2002 Xantrex Technology Inc.
P/N 975-0041-01-02 Rev A 03/02
A-1
APPENDIX A – SPECIFICATIONS
ELECTRICAL SPECIFICATIONS
1
Utility Interactive Protection
Over/under AC voltage and frequency
detection plus active islanding detection
AC Voltage (Nomimal)
120 VAC
AC Voltage (Allowed)
Utility Interactive Mode
106 - 132 VAC
Bypass mode/”Buy” Current
80-149 VAC
Input Frequency (Allowed)
Utility Interactive Mode
59.3 - 60.5 Hz
Bypass Mode/”Buy” Current
53.0 - 67.0 Hz
AC Current (Allowed) (@ 25°C)
Utility Interactive Mode
40 amps continuous
Bypass Mode/”Buy” Current
60 amps continuous
Total Output Harmonic Distortion
Rated
<5% at rated power
Typical
2.5% at rated power
MECHANICAL SPECIFICATIONS
Enclosure Type
Indoor, ventilated, steel chassis with
white, powder-coat finish
Unit Weight
26 lb (15.9 kg)
Dimensions (H x W x D)
6.3" x 21" x 7"
(16 cm x 53.3 cm x 17.8 cm)
Mounting
wall mount in a horizontal position only
AC Input/Output Terminals
Sized for #2-#14 AWG wires
Neutral Bar
Sized for #6 AWG wires
Conduit Sizes
Dual ¾" - 1" and ½" - ¾" knockouts
Specifications @ 25 °C
Specifications subject to change without notice.
1
All electrical specifications are based on the unit operating
in the Utility Interactive Mode (SELL Mode selected)
unless otherwise specified.
Summary of Contents for Trace SW4024
Page 1: ...Installation Guide Grid Tie Interface GTI SW Series SW4024 SW4048 SW5548...
Page 44: ...2 0 INSTALLATION 38 2002 Xantrex Technology Inc P N 975 0041 01 02 Rev A 03 02 Notes...
Page 46: ...3 0 TROUBLESHOOTING 2002 Xantrex Technology Inc P N 975 0041 01 01 Rev A 01 02 40 Notes...
Page 48: ...2002 Xantrex Technology Inc P N 975 0041 01 02 Rev A 03 02 A 2...
Page 53: ......
Page 54: ......
Page 55: ......