2.0 INSTALLATION
16
© 2002 Xantrex Technology Inc.
P/N 975-0041-01-02 Rev A 03/02
Inverter AC Output Wiring to the GTI
WARNING: ENSURE THE SUB-PANEL DOES NOT
HAVE A NEUTRAL-TO-GROUND BOND. IF IT
DOES, REMOVE IT. ALL AC NEUTRAL-GROUND
BONDING IS DONE AT THE MAIN UTILITY PANEL.
1. Connect a NEUTRAL (white) wire to the inverters’s NEUTRAL OUT
terminal.
2 . Connect the other end of this same NEUTRAL wire to the NEUTRAL bar in
the GTI.
3. Connect a HOT (Black) wire to the inverter’s terminal labeled AC HOT
OUTPUT.
4. Connect the other end of the HOT (black) wire from the inverer’s AC HOT
OUT terminal to the GTI’s HOT IN terminal.
5. Torque all connections to 10 to 15 inch-pounds.
See Figure 2-5d for an illustration of the inverter AC output wiring to
the GTI.
Wiring (continued)
AC Wiring for Single-Inverter Installations (continued)