2.0 INSTALLATION
18
© 2002 Xantrex Technology Inc.
P/N 975-0041-01-02 Rev A 03/02
Wiring (continued)
AC Wiring for Single-Inverter Installations (continued)
GTI Wiring to the Sub-Panel
WARNING: ENSURE THE SUB-PANEL DOES NOT
HAVE A NEUTRAL-TO-GROUND BOND. IF IT
DOES, REMOVE IT. ALL AC NEUTRAL-GROUND
BONDING IS DONE AT THE MAIN UTILITY PANEL.
1. Connect a NEUTRAL (white) wire to the GTI’s NEUTRAL bar.
2. Connect the other end of this NEUTRAL wire to the NEUTRAL bar in the
sub-panel.
3. Connect the HOT (black) wire to the GTI’s AC HOT OUT terminal.
4. Connect the other end of this HOT (black) wire to the sub-panels HOT IN
terminal.
5. Torque all the inverter’s connections to 10 to 15 inch-pounds.
NOTE: Consult the sub-panel manufacturer’s
specifications for wire torques on the sub-panel
connections. Use those torque requirements if different.