2.0 INSTALLATION
26
© 2002 Xantrex Technology Inc.
P/N 975-0041-01-02 Rev A 03/02
Wiring (continued)
AC Wiring for Dual-Inverter Installations (continued)
Utility Grid AC Wiring to Dual GTIs
1. Connect a wire from the neutral bus in the main service panel to the
NEUTRAL bar in the GTI-1.
2. Connect a wire to the NEUTRAL bar on the GTI-1 and route this wire to the
GTI-2’s NEUTRAL bar. Keep this wire as short as possible.
3. Select a dual-pole breaker in the main service panel. Connect a wire from
the L1-pole of the selected breaker to the GTI-1’s AC HOT IN terminal.
4. Connect a wire from the L2 pole of the same dual-pole breaker to the GTI-
2’s AC HOT IN terminal.
See Figure 2-8b for an illustration of AC wiring from the utility grid to
the GTIs.