2.0 INSTALLATION
12
© 2002 Xantrex Technology Inc.
P/N 975-0041-01-02 Rev A 03/02
Wiring (continued)
AC Wiring for Single-Inverter Installations (continued)
Utility Grid AC Wiring to the GTI
WARNING: DISCONNECT THE BATTERIES FROM
THE INVERTER IF THEY ARE ALREADY CONNECTED.
1. Ensure the breaker that feeds the GTI is OFF (i.e., no power out). Feed the
HOT and NEUTRAL input wires from the GTI to the main utility panel.
Leave a sufficient amount of extra wire at each end.
2. Confirm a GROUND (green) wire exists from the main utility panel to the
GTI’s AC GROUND lug.
3 . Connect the NEUTRAL (white) wire from the main utility panel to the GTI’s
NEUTRAL bar.
4 . Connect the HOT (BLACK) wire from a single-pole breaker (60 amps) in
the main utility panel to the GTI’s AC1 HOT IN terminal.
5 . Torque all connections to 10 to 15 inch-pounds.
See Figure 2-5b for an illustration of Utility Grid AC Wiring to the GTI.