2.0 INSTALLATION
14
© 2002 Xantrex Technology Inc.
P/N 975-0041-01-02 Rev A 03/02
Inverter AC Input Wiring to the GTI
1. Feed the HOT and NEUTRAL input wires from the inverter to the GTI.
Leave three to six inches of extra wire at each end.
2. Connect the NEUTRAL (white) wire from the GTI’s NEU OUT terminal to
the inverter’s NEUTRAL IN 1 terminal.
3 . Connect the AC1 HOT OUT (BLACK) wire from the GTI to the inverter’s
AC1 HOT IN terminal.
4 . Torque all connections to 10 to 15 inch-pounds.
See Figure 2-5c for an illustration of the inverter AC input wiring to the
GTI.
Wiring (continued)
AC Wiring for Single-Inverter Installations (continued)