AC Wiring for Single-Inverter Installations
NOTE: All wiring should be performed by a qualified
person or a licensed electrician.
NOTE: Ensure that wire size and conduit sizes are
appropriate for this installation. AC wiring should be
routed in separate conduits from the communications
cable.
CAUTION: AC pass-through ability through the GTI
is 60 amps. It is recommended to use minimum
#6 AWG (THHN) wiring.
See Figure 2-7 for an enlargement of this circuit board showing the
location of the communications cable port.
NEUTRAL
Bar
AC IN
from the
inverter output
AC OUT
to the
subpanel
AC OUT
to the
inverter’s
AC HOT IN1
Communications
Cable Port
(behind this cable)
AC IN
from the grid
GROUND
LUG