630140_1
XFIRE_1200_GB_Manual_R
‐
emotion
12.11 Sealing ‘through roof’ and ‘through wall’ penetrations:
For ‘through roof’ penetrations, use a Master Flash flashing or equivalent to create a
weather-tight seal between the flue and the roof cladding.
For ‘through wall’ penetrations, this will require the use of a Wall Thimble. The Wall Thimble
will ensure you have suitable clearance from combustibles as well as sealing the
penetration. The section of the wall thimble installed on the external surface of the wall
should be sealed to the wall using a high temperature sealant such as Envirograf Product
62, Sealocrete Heat Resistant Silicone or equivalent. Additional sealant is required to seal
the Terminal Cap to the external wall. A bead should be run along the edge of the Terminal
that will be in contact with the wall once installed.
12.12
Twist locking procedure:
Before connecting flue components, to ensure an airtight seal run a single 7-8mm bead of
Sealocrete Heat Resistant Silicone, or equivalent, on the ‘male’ end of the flue as
shown in the diagram below.
The four indentations located on the female end of the flue are designed to slide straight
onto the male ends of the adjacent flue length, by orienting the four flue indentations so
they match and slide into the four entry slots on the male ends.
Push the pipe sections completely together, then twist-lock one section clockwise
approximately
one-quarter
turn, until the two sections are fully locked.
Wipe off any excess sealant from the exterior of the flue joint.