Checking Operating Pressure:
WARNING: The regulator that is supplied with the fire MUST NOT BE REMOVED.
Removal of the regulator, or replacing it with one not intended for use with an Escea fire,
will void the limited appliance warranty.
Check the operating pressure at the regulator located at the front LH corner of the
appliance. This is best done before the facia panels have been fitted to avoid facia
damage. Pressure test points are available for both inlet and operating test pressure (as
shown
below).
1)
Remove inlet pressure test point screw and attach manometer tube.
2)
Run the fire on full and measure inlet pressure with all the other gas appliances
running. If pressure does not fall within the pressure tolerances listed on the table
below then the installation pipe size or upstream regulator settings are incorrect.
If the correct supply pressure cannot be obtained, then the fire gas supply must be
disconnected until the fault is corrected.
3)
Remove the manometer and replace inlet test point screw.
4)
Remove the operating pressure test point screw. Connect manometer tube and
measure pressure with fire running on full and with all the other gas appliances
running.
5)
Replace operating pressure test point screw and leak test inlet and operating
pressure test points and inlet gas connection unions.
A
= Inlet gas connection
B
= Inlet pressure test point
C
= Gas Conversion Cap
D
= Operating Pressure test point
XFIRE
1200
Technical
Data
Gas
Type
Propane (G31)
Natural
(G20)
Inlet
Pressure
37
mbar
20
mbar
+
/
‐
1.5
mbar
Operating
Pressure
23
mbar
10
mbar
Injector
size
1.3mm
1.9mm